Digital panel meter PZ5 two-channel measurement
Item description
The PZ5.0001.1540D was designed for the allocation of 2 sensors with direct voltage/ direct current signals. The configuration hap- pens via 4 front keys or via optional PC-soft- ware. The 5-digit display shows the measure- ments, respectively the calculated value of the measured variable. Optionally available are 4 changeover relays for the monitoring of limit values, interfaces RS232/RS485 for data trans- fer to/from the device and analog outputs 0-10VDC, 4-20mA or 0-20mA for further evalu- ation. Selectable software functions, an ex- ternal channel switching, also a 24Bit resolu- tion characterise an established device for industrial use.
Technical Data
Housing | 96 x 48 mm |
Display | 5-digit 14 mm digit height Colour: red |
Range displayed | -9999...99999 |
Operation | front panel keyboard protection class IP54 |
Input | 2x 0/4-20mA, 0-10VDC Digital input: <2.4V OFF, >10V ON, max. 30 VDC |
Analogue Output | 0-20 mA Burden ≤500Ohm 12Bit 4-20 mA Burden ≤500Ohm 12Bit 0-10 VDC Burden ≥100kOhm 12Bit |
Switch point | 2 or 4 relays (change-over contacts) 250 V / 5 AAC, 30 V / 5 ADC |
Interface | RS232 or RS485 galvanic isolated |
Power supply | 230 VAC 24 VDC +/-10% galvanic isolated |
Sensor supply | 10 VDC / 20 mA 24 VDC / 50 mA |
Software properties |
|
Downloads | Data sheet and price list Manual |